State of the art chlorine leak Neutralization system for an American chemical company

State of the art chlorine leak Neutralization system for an American chemical company

IEC has designed, supplied and validated a 2250 kg/hour chlorine leak absorption system for a premium American chemicals company. The contract required IEC to conduct a trial run at site with actual leaked chlorine at this rate. The outlet concentration of the treated gases was less than 0.1 PPM, well below the acceptable emission rate.

The system featured our proprietary 2 stage scrubbing system controlled with a touch screen PLC. The primary stage is an ejector scrubber capable of entrainment and neutralization of large leaks. The second stage is a polishing tower capable of picking-up the fine strains of chlorine from the mixture of gases.

The system is a 24 x 7 continuous operation with a system response time of less than 5 seconds. The blowers and pumps are VFD operated to ramp up during duty and ramp down during normal ventilation process.